Size a marine conductor the right way — by current (ampacity) AND by run length (voltage drop), per ABYC E-11-2025. Enter the load, the one-way run and the conditions; it returns the AWG you need.
Based on ABYC E-11-2025: 105°C tinned-copper conductor ampacity (outside-engine-space table) with temperature & bundling derates, and the 3% / 10% voltage-drop limits. Always use marine-grade tinned, finely-stranded wire. Verify against the current ABYC tables for the exact insulation and conditions.
| AWG | Ampacity (105°C, outside ER) |
|---|---|
| 18 | 20 A |
| 16 | 25 A |
| 14 | 35 A |
| 12 | 45 A |
| 10 | 60 A |
| 8 | 80 A |
| 6 | 120 A |
| 4 | 160 A |
| 2 | 210 A |
| 1 | 245 A |
| 1/0 | 285 A |
| 2/0 | 330 A |
| 3/0 | 385 A |
| 4/0 | 445 A |