ESIEssential Shipyard UniversityCondition & Value Survey
Field form · Condition & Value · sail and power

ESI Condition & Value Survey

Every point carries its bound standard, so you never look a citation up in the field — and the moment a point is anything but green, the standard it fails is put in front of you. You record what you saw and how it failed; the flag derives itself.

223inspection points
Derivedseverity
11engine forms linked
→ deskemailed
How ESI runs a survey
  1. Start at the top and work down. Rig, then deck, then topsides, then waterline, then bottom. Water travels down — work the same direction and you find the source, not just the stain.
  2. Start at the bow and work back. Every section, every compartment, same direction, every time. A route you repeat is a route you can prove you completed.
  3. Use your tools wisely. Where ESI already has a tool, use it. A number off the Go/No-Go tool or the wire calculator beats an opinion, and it is what makes the finding survive a challenge.
  4. Finish as you go. Write the finding at the point, photograph it while you are standing there. A survey completed on the boat is a report that never needs a second visit.
Vessel type

Sail vessels get §18. On a power vessel that section is hidden and is not counted against you.

📄§0 · Scope, conduct and disclosure

Agreed and signed before the survey — not delivered after it.

Surveyor independence & disclosure
The surveyor is employed by Essential Shipyard Industries, a working boatyard. Notwithstanding that employment, this survey is rendered independently: the surveyor’s findings, classifications and conclusions are formed with full professional autonomy; the surveyor is not compensated on the basis of findings; and the yard exercises no input, direction, or influence over the survey’s observations or conclusions. Any repair or recommendation arising from this survey may be carried out by any qualified yard of the client’s choosing.
ESI does not use the word “appears.” The benchmark survey defines it as “a close inspection was not possible” and then uses it dozens of times as though it were a finding. Here, a point you could not inspect is GREY with a reason, and a point you inspected but could not confirm is UNVERIFIABLE. Those are different states, they are recorded in different places, and neither of them quietly reads as a pass.
Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.

📏§A2 · Instrumentation, calibration and settings

Fill this in before you touch the boat. An instrument with no settings recorded produces a picture, not a measurement.

Overclaiming from an instrument is the fastest route to a liability claim. Every reading in this report is reported with the instrument, the setting and the reference it was read against — which is what makes it a measurement rather than an impression.
📏 Instrument use and settings
Moisture meter — contact
  • It is comparative, not absolute. A number on its own is not a finding. Establish a baseline on a known-dry area of the same laminate, record it, and report every reading against that baseline.
  • Record the scale. Meters do not share a scale. “22” means nothing without the make, model and scale it was read on.
  • Record time since haul. A bottom straight out of the water reads high everywhere. Note the hours since haul-out and the weather — without it the reading is not defensible.
  • Surface must be clean and dry. Wet paint, growth and a damp rag all read as wet laminate.
  • Temperature shifts readings. Record ambient and surface temperature if either is unusual.
Moisture meter — non-contact / capacitance
  • Record the depth setting. Shallow mode reads the skin and gelcoat; deep mode reads into the laminate and core. They answer different questions and they disagree — a report that does not say which mode was used cannot be repeated.
  • Record the sensitivity / range setting as well as the depth mode.
  • Zero it on air, then on a known-dry reference of the same construction before you take a single reading that goes in the report.
  • It must sit flat. Curvature, voids and a gap under the pad all produce false highs.
  • It cannot tell water from metal. Backing plates, foil-faced insulation, tank walls and wiring behind the laminate all read wet. Confirm with a second method — sounding, or a contact meter — before you flag it.
  • Confirm before flagging. A single non-contact high reading is UNVERIFIABLE, not DEGRADED. It becomes degraded when a second method agrees or you cite a limit.
Thermal imager (IR camera)
  • An IR image without emissivity and reflected temperature is a picture, not data. Record both, every time, or the image is inadmissible as a measurement.
  • Set emissivity for the material. Painted GRP is around 0.95. Bare or polished metal is low and unreliable — put a tape target or a spot of paint on it and image that.
  • Record reflected apparent temperature and ambient.
  • Load the circuit before imaging electrical. A cold panel proves nothing except that nothing was drawing current.
  • Work in ΔT, not absolute. Compare a component against an identical adjacent one — terminal to terminal, cylinder to cylinder. The difference is the finding.
  • Sun loading and reflections make false hot spots. Shade it, or image it early.
IR temperature gun / pyrometer
  • Mind the spot-size ratio. At distance you are averaging a much larger area than you think, and the hot spot disappears into it. Get close, or use the imager.
  • Same emissivity problem as the imager — bare exhaust metal and polished manifolds read low.
  • Use it comparatively: cylinder to cylinder on the exhaust manifold, riser to riser, bearing to bearing. Record every reading in the set, not just the odd one.
Sounding hammer / percussion
  • Plastic or phenolic head only. Never steel on gelcoat — you will make the defect you are looking for.
  • Listen for a change in tone, not an absolute tone. Sharp and ringing means attached; dull and flat means disbond, void or wet core.
  • Consistent grid, consistent force, consistent drop height. Inconsistent technique produces inconsistent tone and a finding you cannot defend.
  • Mark, photograph and record the extent. “Some softness” is not a finding. A marked and photographed area with dimensions is.
  • Sound and moisture-meter together. Either one alone is weak; agreement between them is what makes DEGRADED defensible.
Battery tester and ripple-current test
  • Enter the battery’s rated CCA. A conductance tester without the correct rating printed on the battery entered into it returns a meaningless number.
  • Remove surface charge first — rest the battery, or apply a brief load. Testing straight off a charger reads high and passes bad batteries.
  • Test at the posts, not at the switch or the bus bar, or you are testing the cable.
  • Record state of charge and state of health separately. They are different findings: a discharged good battery and a charged dead one look the same on a voltmeter.
  • Ripple test — this is the one nobody else does. With the engine running at charging rpm, read AC volts across the DC bus. Elevated AC ripple on a DC system means failing alternator diodes. Record the mV reading and the rpm it was taken at.
  • Record the ripple figure even when it is good. That is a GREEN with a measurement behind it, and it is the kind of verification the incumbent report has none of.
Combustible gas detector / fuel sniffer
  • Bump-test before use. An un-bumped detector is an unverified instrument, and anything it tells you is UNVERIFIABLE. Record the bump test and the calibration date.
  • Sniff before you ventilate. Open the boat up first and you have destroyed the evidence. This is the single most common way the test gets wasted.
  • Sniff low. Gasoline vapour and propane are heavier than air — they sit in the bilge, under the sole, and in the bottom of the LPG locker.
  • Test the LPG locker drain, the bilge under the tanks, and the engine compartment before the blower runs.
  • A positive reading is a stop-work. Do not continue the survey, do not run anything electrical, get people off, and tell the desk.
Digital multimeter and corrosion reference
  • Record make and model. It goes in the instrumentation manifest like everything else.
  • Silver / silver-chloride half-cell for corrosion potential. The benchmark survey we compared against states plainly that a corrosion meter was not used — and then gives an opinion on the bonding system anyway. If you do not run the reference cell, the bonding system is UNVERIFIABLE and it is recorded as such.
  • Record the reference electrode type and the reading location. Readings are not comparable between electrode types.
Moisture — contact meter
Moisture — non-contact / capacitance
Thermal and temperature
Percussion
Electrical
Gas detection
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
Other

🛥§1 · General information and vessel identity

Get this wrong and every finding attaches to the wrong hull.

33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.

🛠§2 · Hull, deck and superstructure

Top down, bow to stern. Same route every time.

📏 Instrument use and settings
Moisture meter — contact
  • It is comparative, not absolute. A number on its own is not a finding. Establish a baseline on a known-dry area of the same laminate, record it, and report every reading against that baseline.
  • Record the scale. Meters do not share a scale. “22” means nothing without the make, model and scale it was read on.
  • Record time since haul. A bottom straight out of the water reads high everywhere. Note the hours since haul-out and the weather — without it the reading is not defensible.
  • Surface must be clean and dry. Wet paint, growth and a damp rag all read as wet laminate.
  • Temperature shifts readings. Record ambient and surface temperature if either is unusual.
Moisture meter — non-contact / capacitance
  • Record the depth setting. Shallow mode reads the skin and gelcoat; deep mode reads into the laminate and core. They answer different questions and they disagree — a report that does not say which mode was used cannot be repeated.
  • Record the sensitivity / range setting as well as the depth mode.
  • Zero it on air, then on a known-dry reference of the same construction before you take a single reading that goes in the report.
  • It must sit flat. Curvature, voids and a gap under the pad all produce false highs.
  • It cannot tell water from metal. Backing plates, foil-faced insulation, tank walls and wiring behind the laminate all read wet. Confirm with a second method — sounding, or a contact meter — before you flag it.
  • Confirm before flagging. A single non-contact high reading is UNVERIFIABLE, not DEGRADED. It becomes degraded when a second method agrees or you cite a limit.
Sounding hammer / percussion
  • Plastic or phenolic head only. Never steel on gelcoat — you will make the defect you are looking for.
  • Listen for a change in tone, not an absolute tone. Sharp and ringing means attached; dull and flat means disbond, void or wet core.
  • Consistent grid, consistent force, consistent drop height. Inconsistent technique produces inconsistent tone and a finding you cannot defend.
  • Mark, photograph and record the extent. “Some softness” is not a finding. A marked and photographed area with dimensions is.
  • Sound and moisture-meter together. Either one alone is weak; agreement between them is what makes DEGRADED defensible.
2.1 Hull construction
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
2.2 Transom
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
2.3 Deck construction and fittings
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC H-40-2024 - Anchoring, Mooring & Strong Points designation unconfirmed
Ground tackle attachment and load path into the structure.
  • Anchoring strong points able to take the design load with backing plates.
  • Load path carried into structure, not into the deck skin alone.
  • Rode secured at the bitter end to the vessel.
  • Chocks and rollers arranged so the rode does not chafe under load.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

🛏§3 · Cabin appointments and galley

Habitability, and the water intrusion evidence that lives inside.

General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC A-7-2021 - Boat Heating Systems
Fuel-burning heaters: exhaust, fuel supply, controls, CO risk.
  • Fuel-burning heater exhaust routed and terminated so products cannot re-enter the accommodation.
  • Combustion air supply independent of the accommodation where required.
  • Fuel supply with a shut-off, and no joints in concealed spaces.
  • CO detection in spaces served by the heater.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

⚙️§4 · Propulsion machinery

You have a purpose-built form for this. Use it, attach it, roll the findings up here.

Note

The benchmark survey we compared against had a separate engine surveyor aboard and referred all machinery questions to that report. That is the market ESI already sells into — which is why the machinery track ships first.

🔧 Mechanical set — stop here and use the engine survey
There is a purpose-built form for every engine below. Open it, complete it, attach it to this report, and bring only the roll-up findings back. Do not re-derive machinery condition in the C&V.
Engine not listed? Complete the general points below, record what you could not verify, and flag it to the desk so a form gets built.
🔨 Ready-made ESI tools for this section
Runout and scoring to ACCEPT / CAUTION / REJECT against ABYC P-6-2021. The sample survey we benchmarked said only “some sloppiness when upward pressure applied.” This gives you a number instead.
Shaft Go / No-Go Tool
Printable sheet - stern tube, shaft, coupler, cutless, seal, gearbox ratio.
Drivetrain Measurement (Ref A)
General fastener torque, dry and lubed. Where the OEM publishes a joint spec, the joint spec wins.
Bolt Torque Tool
📏 Instrument use and settings
IR temperature gun / pyrometer
  • Mind the spot-size ratio. At distance you are averaging a much larger area than you think, and the hot spot disappears into it. Get close, or use the imager.
  • Same emissivity problem as the imager — bare exhaust metal and polished manifolds read low.
  • Use it comparatively: cylinder to cylinder on the exhaust manifold, riser to riser, bearing to bearing. Record every reading in the set, not just the odd one.
Thermal imager (IR camera)
  • An IR image without emissivity and reflected temperature is a picture, not data. Record both, every time, or the image is inadmissible as a measurement.
  • Set emissivity for the material. Painted GRP is around 0.95. Bare or polished metal is low and unreliable — put a tape target or a spot of paint on it and image that.
  • Record reflected apparent temperature and ambient.
  • Load the circuit before imaging electrical. A cold panel proves nothing except that nothing was drawing current.
  • Work in ΔT, not absolute. Compare a component against an identical adjacent one — terminal to terminal, cylinder to cylinder. The difference is the finding.
  • Sun loading and reflections make false hot spots. Shade it, or image it early.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
ABYC P-4 - Inboard Engines & Transmissions
Engine mounting, guarding of rotating parts, belts, controls.
  • Engine secured to bearers able to take thrust and torque.
  • Rotating parts guarded where a person can reach them.
  • Controls operate ahead, neutral and astern positively, and return to neutral.
  • Engine can be shut down from the helm.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC H-32-2023 - Ventilation, Diesel
Engine compartment ventilation on diesel vessels.
  • Natural ventilation for diesel engine compartments sized to the compartment.
  • Air supply adequate for combustion as well as cooling.
  • Openings positioned so a following sea cannot down-flood them.
ABYC P-1-2025 - Marine Wet Exhaust Systems
Exhaust hose, riser and mixing elbow, water injection, backpressure.
  • Wet exhaust hose rated for the service and double clamped at each connection.
  • Riser or injection point high enough above the waterline to keep water out of the cylinders (verify the figure).
  • No low spots that trap water between the injection point and the transom.
  • Supported so the hose is not carrying the weight of the muffler or run.
  • Lagging intact on dry sections — an exposed dry riser is a burn and fire risk.
ABYC P-1-2025 - Marine Wet Exhaust Systems
Exhaust hose, riser and mixing elbow, water injection, backpressure.
  • Wet exhaust hose rated for the service and double clamped at each connection.
  • Riser or injection point high enough above the waterline to keep water out of the cylinders (verify the figure).
  • No low spots that trap water between the injection point and the transom.
  • Supported so the hose is not carrying the weight of the muffler or run.
  • Lagging intact on dry sections — an exposed dry riser is a burn and fire risk.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC P-4 - Inboard Engines & Transmissions
Engine mounting, guarding of rotating parts, belts, controls.
  • Engine secured to bearers able to take thrust and torque.
  • Rotating parts guarded where a person can reach them.
  • Controls operate ahead, neutral and astern positively, and return to neutral.
  • Engine can be shut down from the helm.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
Transmission
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Shafting and stern gear
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.

⛽§5 · Fuel system

Fire and explosion live in this section.

📏 Instrument use and settings
Combustible gas detector / fuel sniffer
  • Bump-test before use. An un-bumped detector is an unverified instrument, and anything it tells you is UNVERIFIABLE. Record the bump test and the calibration date.
  • Sniff before you ventilate. Open the boat up first and you have destroyed the evidence. This is the single most common way the test gets wasted.
  • Sniff low. Gasoline vapour and propane are heavier than air — they sit in the bilge, under the sole, and in the bottom of the LPG locker.
  • Test the LPG locker drain, the bilge under the tanks, and the engine compartment before the blower runs.
  • A positive reading is a stop-work. Do not continue the survey, do not run anything electrical, get people off, and tell the desk.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
ABYC H-33-2021 - Diesel Fuel Systems
Tanks, lines, filters and separators, connections, leak prevention.
  • Tanks labelled, supported, and accessible for inspection.
  • Fuel hose carrying the correct type marking and within its date.
  • Shut-off valve at the tank, accessible.
  • Fill and vent arranged so fuel cannot be taken aboard into the bilge.
  • Filters and separators mounted so they can be serviced without spilling into the bilge.
ABYC H-24-2025 - Gasoline Fuel Systems designation unconfirmed
Gasoline tanks, lines, vents, ignition protection.
  • Every electrical component in a gasoline compartment must be ignition protected.
  • Metallic fill, tank and fuel system grounded to prevent static discharge.
  • Anti-siphon protection where the tank can siphon into the engine.
  • Vent discharging outboard, clear of openings into the hull.
ABYC H-2 - Ventilation, Gasoline
Engine and tank compartment ventilation where gasoline is present.
  • Powered and natural ventilation for gasoline engine and tank compartments.
  • Blower run before starting, with a label at the helm saying so.
  • Intake and exhaust ducting positioned to actually change the air in the bilge, not the top of the compartment.
ABYC H-24-2025 - Gasoline Fuel Systems designation unconfirmed
Gasoline tanks, lines, vents, ignition protection.
  • Every electrical component in a gasoline compartment must be ignition protected.
  • Metallic fill, tank and fuel system grounded to prevent static discharge.
  • Anti-siphon protection where the tank can siphon into the engine.
  • Vent discharging outboard, clear of openings into the hull.

🔋§6 · Electrical systems — DC and AC

Wire, protection, and the connections between them.

🔨 Ready-made ESI tools for this section
Load and run length to AWG by ampacity and voltage drop. Turns “appears adequate” into a cited figure.
Wire Calculator (ABYC)
Charging hardware fitment check.
Alternator Fitment & Crossover
📏 Instrument use and settings
Battery tester and ripple-current test
  • Enter the battery’s rated CCA. A conductance tester without the correct rating printed on the battery entered into it returns a meaningless number.
  • Remove surface charge first — rest the battery, or apply a brief load. Testing straight off a charger reads high and passes bad batteries.
  • Test at the posts, not at the switch or the bus bar, or you are testing the cable.
  • Record state of charge and state of health separately. They are different findings: a discharged good battery and a charged dead one look the same on a voltmeter.
  • Ripple test — this is the one nobody else does. With the engine running at charging rpm, read AC volts across the DC bus. Elevated AC ripple on a DC system means failing alternator diodes. Record the mV reading and the rpm it was taken at.
  • Record the ripple figure even when it is good. That is a GREEN with a measurement behind it, and it is the kind of verification the incumbent report has none of.
Thermal imager (IR camera)
  • An IR image without emissivity and reflected temperature is a picture, not data. Record both, every time, or the image is inadmissible as a measurement.
  • Set emissivity for the material. Painted GRP is around 0.95. Bare or polished metal is low and unreliable — put a tape target or a spot of paint on it and image that.
  • Record reflected apparent temperature and ambient.
  • Load the circuit before imaging electrical. A cold panel proves nothing except that nothing was drawing current.
  • Work in ΔT, not absolute. Compare a component against an identical adjacent one — terminal to terminal, cylinder to cylinder. The difference is the finding.
  • Sun loading and reflections make false hot spots. Shade it, or image it early.
6.1 DC system
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems for this point
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Meter on AC volts, probes across the DC bus, engine running at charging rpm.
  • A healthy alternator gives a low AC reading on the DC bus. A high reading means one or more diodes have failed.
  • Record the millivolt figure AND the rpm it was read at — a number without the rpm is not repeatable.
  • Confirm the acceptance threshold against the alternator maker's data before calling it a finding (confirm).
  • Record the figure even when it passes. That is a GREEN with a measurement behind it, and almost no incumbent report has one.
ABYC E-13-2025 - Lithium Ion Batteries
Lithium house banks: BMS, protection, installation, charge control.
  • Lithium banks require a BMS able to disconnect on over-voltage, under-voltage, over-current and temperature.
  • Charging sources must be controlled so the BMS is not the routine disconnect.
  • Installation location, ventilation and mounting per the maker's instructions.
  • Confirm the vessel's charging system was reconfigured when the bank was converted — a drop-in swap is a finding.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems for this point
Conductor size and routing, over-current protection, grounds, connections, charging.
  • The fuse protects the CONDUCTOR, not the device. Size it to the wire, then check the device is separately protected.
  • Over-current protection within 7 in of the connection to the source of power (confirm against current edition).
  • Up to 40 in if the conductor is contained throughout its length in a sheath or enclosure (confirm).
  • Longer allowance for cranking-motor conductors, and engine-cranking circuits carry their own exceptions (confirm).
  • AIC rating must exceed the bank's available short-circuit current. This is the one people miss on lithium and large AGM banks — a 5,000 A fuse on a bank that can deliver more is not protection.
  • A battery switch is NOT over-current protection. If the only thing between the bank and the boat is a switch, the mode is ABSENT.
  • Protection goes on the positive conductor, as close to the battery as practicable.
ABYC E-11-2025 - AC & DC Electrical Systems for this point
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Size for BOTH ampacity and voltage drop, then take the larger wire. Ampacity alone passes wire that browns out the load.
  • 3% voltage drop for panelboard feeds, navigation lights, electronics and other critical circuits (confirm).
  • 10% for non-critical loads (confirm).
  • Length is the round trip — positive plus return, not one-way. Halving it is the most common error in the field.
  • Derate for engine-space temperature and for bundling. A conductor correct on the chart can be undersized in a hot engine room.
  • Use the ESI Wire Calculator and put the resulting AWG and the drop figure in the measurement field.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
6.2 AC system
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.
6.3 Generator and inverter
ABYC P-1-2025 - Marine Wet Exhaust Systems
Exhaust hose, riser and mixing elbow, water injection, backpressure.
  • Wet exhaust hose rated for the service and double clamped at each connection.
  • Riser or injection point high enough above the waterline to keep water out of the cylinders (verify the figure).
  • No low spots that trap water between the injection point and the transom.
  • Supported so the hose is not carrying the weight of the muffler or run.
  • Lagging intact on dry sections — an exposed dry riser is a burn and fire risk.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.

🚿§7 · Fresh water system

General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

🚽§8 · Sanitation — black and grey water

Federal requirements live here.

33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.

🎛§9 · Steering system

Safety-critical. Deficiencies here do not get deferred to the next haul.

General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.

🪝§10 · Ground tackle

ABYC H-40-2024 - Anchoring, Mooring & Strong Points designation unconfirmed
Ground tackle attachment and load path into the structure.
  • Anchoring strong points able to take the design load with backing plates.
  • Load path carried into structure, not into the deck skin alone.
  • Rode secured at the bitter end to the vessel.
  • Chocks and rollers arranged so the rode does not chafe under load.
ABYC H-40-2024 - Anchoring, Mooring & Strong Points designation unconfirmed
Ground tackle attachment and load path into the structure.
  • Anchoring strong points able to take the design load with backing plates.
  • Load path carried into structure, not into the deck skin alone.
  • Rode secured at the bitter end to the vessel.
  • Chocks and rollers arranged so the rode does not chafe under load.
ABYC H-40-2024 - Anchoring, Mooring & Strong Points designation unconfirmed
Ground tackle attachment and load path into the structure.
  • Anchoring strong points able to take the design load with backing plates.
  • Load path carried into structure, not into the deck skin alone.
  • Rode secured at the bitter end to the vessel.
  • Chocks and rollers arranged so the rode does not chafe under load.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC H-40-2024 - Anchoring, Mooring & Strong Points designation unconfirmed
Ground tackle attachment and load path into the structure.
  • Anchoring strong points able to take the design load with backing plates.
  • Load path carried into structure, not into the deck skin alone.
  • Rode secured at the bitter end to the vessel.
  • Chocks and rollers arranged so the rode does not chafe under load.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

🚰§12 · Through-hulls and sea valves

The system most often implicated in sinking claims. Count them, then operate every one.

ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs for this point designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Operate every one, through full travel, by hand and without tools.
  • A valve that will not move is NON-FUNCTIONAL. A valve you did not operate is not a pass — it is GREY with a reason.
  • Check the handle is present and indicates open/closed correctly.
  • Look for a bonding conductor where the installation uses one.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs for this point designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Two clamps at each below-waterline hose connection where the hose end is long enough to take them.
  • All-metal band and screw, corrosion resistant. Perforated-band clamps are not acceptable.
  • Clamps offset so the screw housings are not aligned.
  • One clamp where two are required is NON-COMPLIANT INSTALLATION, not ABSENT — the joint exists and functions.
ABYC H-27-2021 - Seacocks, Thru-Hulls & Drain Plugs designation unconfirmed
Below-waterline penetrations: seacock strength and operation, hose, double clamping.
  • Below-waterline seacocks must operate through full travel without tools.
  • Two clamps at each below-waterline hose connection where the hose end allows.
  • Corrosion-resistant clamps, all-metal band and screw. Perforated-band clamps are not acceptable.
  • Materials compatible below the waterline — plain brass dezincifies and is a finding.
  • Seacock able to take a static load applied at the inboard end (verify the figure).
  • Accessible for operation and service without dismantling joinery.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

⚡§13 · Bonding and cathodic protection

This is the section the benchmark survey admitted it did not measure.

📏 Instrument use and settings
Digital multimeter and corrosion reference
  • Record make and model. It goes in the instrumentation manifest like everything else.
  • Silver / silver-chloride half-cell for corrosion potential. The benchmark survey we compared against states plainly that a corrosion meter was not used — and then gives an opinion on the bonding system anyway. If you do not run the reference cell, the bonding system is UNVERIFIABLE and it is recorded as such.
  • Record the reference electrode type and the reading location. Readings are not comparable between electrode types.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.
ABYC E-2-2025 - Cathodic Protection for this point
Bonding and sacrificial anodes on underwater metals.
  • Silver / silver-chloride reference cell in the water, meter negative to the cell, positive to the bonding system.
  • Record every reading location and the electrode type — readings from different electrode types are not comparable.
  • Protected potential ranges differ by metal. Confirm the target band for the metal you are measuring (confirm).
  • Over-protection is also a finding on aluminium drives — it lifts paint and generates hydrogen.
  • If you did not carry the cell, this point is GREY with that reason. Do not give an opinion on the bonding system without it.
ABYC E-2-2025 - Cathodic Protection for this point
Bonding and sacrificial anodes on underwater metals.
  • Zinc for salt, aluminium for brackish, magnesium for fresh.
  • Magnesium on a salt-water boat depletes very fast and can over-protect and blister paint. That is NON-COMPLIANT INSTALLATION, not wear.
  • Aluminium is the general-purpose choice and is acceptable in salt as well as brackish.
  • Read the casting mark rather than guessing from colour.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.
ABYC E-11-2025 - AC & DC Electrical Systems
Conductor size and routing, over-current protection, grounds, connections, charging.
  • Conductors sized for BOTH ampacity and voltage drop — 3% for critical circuits, 10% non-critical (verify).
  • Over-current protection close to the source of power (verify the distance allowance).
  • No wire nuts or twist-on connectors. Ring or captive spade terminals.
  • Conductors supported at intervals and protected from chafe where they pass through structure.
  • AC and DC conductors not run in the same bundle without separation.
  • Batteries secured against tilt; positive terminals insulated against accidental shorting.

🧯§14 · Safety equipment

33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ABYC A-24-2025 - Carbon Monoxide Detection for this point
CO alarms in accommodation spaces.
  • One in each accommodation space with a sleeping berth.
  • Listed for marine use. A household smoke-and-CO unit from a hardware store is a finding.
  • Within its service life — CO sensors expire, typically 5-7 years from manufacture (confirm on the unit).
  • Press to test. Present but silent is NON-FUNCTIONAL, which at class B derives to RED.
NFPA - fire protection designation unconfirmed
Referenced alongside ABYC in survey conduct statements. Confirm the applicable document and edition.
  • Referenced alongside ABYC in the conduct-of-survey statement.
  • Confirm which NFPA document and edition applies before citing it.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
33 / 46 CFR - Federal requirement designation unconfirmed
Mandatory federal regulation. Non-compliance is unlawful, not merely substandard.
  • HIN permanently affixed and matching the documentation.
  • Capacity and certification plate present where required.
  • PFDs, throwable, extinguishers, visual distress signals and sound device to the carriage requirements.
  • Navigation lights of the correct type showing the correct arcs.
  • MSD of a certified type, with the Y-valve secured where required.
  • Backfire flame arrestor and ventilation on gasoline installations.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

💧§15 · Bilge and dewatering

ABYC H-22-2025 - Bilge Pumps designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Dewatering capacity appropriate to the vessel — capacity you cannot determine is UNVERIFIABLE, not green.
  • Automatic operation with a float or equivalent, independent of the panel switch.
  • Discharge above the waterline with anti-siphon protection.
  • Wiring and over-current protection to E-11, and powered independently of the main switch.
ABYC H-22-2025 - Bilge Pumps for this point designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Capacity is rated at zero head. Real output through the installed hose and lift is far lower.
  • If the pump is unmarked and you cannot establish the rating, that is UNVERIFIABLE — it is never GREEN.
  • Check the discharge hose ID matches the pump outlet; a reducer kills the flow the rating implies.
  • Confirm the required capacity for the vessel against the standard before flagging it as inadequate (confirm).
ABYC H-22-2025 - Bilge Pumps designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Dewatering capacity appropriate to the vessel — capacity you cannot determine is UNVERIFIABLE, not green.
  • Automatic operation with a float or equivalent, independent of the panel switch.
  • Discharge above the waterline with anti-siphon protection.
  • Wiring and over-current protection to E-11, and powered independently of the main switch.
ABYC H-22-2025 - Bilge Pumps designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Dewatering capacity appropriate to the vessel — capacity you cannot determine is UNVERIFIABLE, not green.
  • Automatic operation with a float or equivalent, independent of the panel switch.
  • Discharge above the waterline with anti-siphon protection.
  • Wiring and over-current protection to E-11, and powered independently of the main switch.
ABYC H-22-2025 - Bilge Pumps designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Dewatering capacity appropriate to the vessel — capacity you cannot determine is UNVERIFIABLE, not green.
  • Automatic operation with a float or equivalent, independent of the panel switch.
  • Discharge above the waterline with anti-siphon protection.
  • Wiring and over-current protection to E-11, and powered independently of the main switch.
ABYC H-22-2025 - Bilge Pumps designation unconfirmed
Dewatering capacity, switching, discharge, wiring.
  • Dewatering capacity appropriate to the vessel — capacity you cannot determine is UNVERIFIABLE, not green.
  • Automatic operation with a float or equivalent, independent of the panel switch.
  • Discharge above the waterline with anti-siphon protection.
  • Wiring and over-current protection to E-11, and powered independently of the main switch.

🔥§16 · LPG / CNG system

📏 Instrument use and settings
Combustible gas detector / fuel sniffer
  • Bump-test before use. An un-bumped detector is an unverified instrument, and anything it tells you is UNVERIFIABLE. Record the bump test and the calibration date.
  • Sniff before you ventilate. Open the boat up first and you have destroyed the evidence. This is the single most common way the test gets wasted.
  • Sniff low. Gasoline vapour and propane are heavier than air — they sit in the bilge, under the sole, and in the bottom of the LPG locker.
  • Test the LPG locker drain, the bilge under the tanks, and the engine compartment before the blower runs.
  • A positive reading is a stop-work. Do not continue the survey, do not run anything electrical, get people off, and tell the desk.
ABYC A-1-2023 - LPG (Propane) Systems for this point designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Locker vapour-tight to the interior of the boat. Propane is heavier than air and will find any opening.
  • Drain at the very bottom of the locker, discharging overboard above the waterline.
  • Drain must not terminate where the vapour can re-enter the hull — check where it actually exits.
  • Locker opens only to the atmosphere, and the lid seals.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.
ABYC A-1-2023 - LPG (Propane) Systems designation unconfirmed
Locker, drain, regulator, solenoid, tubing, appliance shut-off.
  • Bottle locker vapour-tight to the interior of the boat, opening only to the atmosphere.
  • Drain at the bottom of the locker, discharging overboard above the waterline.
  • Solenoid at the bottle, with a remote switch and indicator at the appliance.
  • Continuous tubing with no joints inside accommodation spaces.
  • Pressure-drop leak test is the acceptance test — not a soap check.

⚓§17 · Out-of-water inspection

Bow to stern along the bottom, then the running gear.

🔨 Ready-made ESI tools for this section
Runout and scoring to ACCEPT / CAUTION / REJECT against ABYC P-6-2021. The sample survey we benchmarked said only “some sloppiness when upward pressure applied.” This gives you a number instead.
Shaft Go / No-Go Tool
📏 Instrument use and settings
Moisture meter — contact
  • It is comparative, not absolute. A number on its own is not a finding. Establish a baseline on a known-dry area of the same laminate, record it, and report every reading against that baseline.
  • Record the scale. Meters do not share a scale. “22” means nothing without the make, model and scale it was read on.
  • Record time since haul. A bottom straight out of the water reads high everywhere. Note the hours since haul-out and the weather — without it the reading is not defensible.
  • Surface must be clean and dry. Wet paint, growth and a damp rag all read as wet laminate.
  • Temperature shifts readings. Record ambient and surface temperature if either is unusual.
Moisture meter — non-contact / capacitance
  • Record the depth setting. Shallow mode reads the skin and gelcoat; deep mode reads into the laminate and core. They answer different questions and they disagree — a report that does not say which mode was used cannot be repeated.
  • Record the sensitivity / range setting as well as the depth mode.
  • Zero it on air, then on a known-dry reference of the same construction before you take a single reading that goes in the report.
  • It must sit flat. Curvature, voids and a gap under the pad all produce false highs.
  • It cannot tell water from metal. Backing plates, foil-faced insulation, tank walls and wiring behind the laminate all read wet. Confirm with a second method — sounding, or a contact meter — before you flag it.
  • Confirm before flagging. A single non-contact high reading is UNVERIFIABLE, not DEGRADED. It becomes degraded when a second method agrees or you cite a limit.
Sounding hammer / percussion
  • Plastic or phenolic head only. Never steel on gelcoat — you will make the defect you are looking for.
  • Listen for a change in tone, not an absolute tone. Sharp and ringing means attached; dull and flat means disbond, void or wet core.
  • Consistent grid, consistent force, consistent drop height. Inconsistent technique produces inconsistent tone and a finding you cannot defend.
  • Mark, photograph and record the extent. “Some softness” is not a finding. A marked and photographed area with dimensions is.
  • Sound and moisture-meter together. Either one alone is weak; agreement between them is what makes DEGRADED defensible.
Wetted surface
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Below-waterline machinery
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
ABYC P-6-2021 - Propeller Shafting Systems
Shaft, coupling, alignment, stuffing box or seal, cutless bearing.
  • Shaft material and diameter suited to the power and bearing spacing.
  • Coupling alignment inside the published tolerance — measured with feeler gauge, not judged by feel.
  • Cutless bearing play measured against the wear limit, not estimated.
  • Stuffing box or seal correctly adjusted, hose double clamped, no continuous drip on a dripless.
  • Shaft supported so there is no visible deflection under load.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
ABYC E-2-2025 - Cathodic Protection
Bonding and sacrificial anodes on underwater metals.
  • Underwater metals bonded to a common conductor with continuity you can measure.
  • Anode material matched to the water — magnesium fresh, aluminium brackish, zinc salt.
  • Anodes mounted on clean bright metal with a confirmed electrical path.
  • Corrosion potential measured with a silver/silver-chloride reference cell — without it, the system is UNVERIFIABLE.

⛵§18 · Rig and standing rigging — sail only

Hidden automatically on a power vessel.

Note

No ESI course covers rigging yet. Findings here rest on surveyor judgement until that gap is closed — flag anything you are unsure of rather than guessing a classification.

General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.

⚓Standing rigging — construction & rod limitation

Rod and stranded wire fail differently and are inspected differently. Select the construction — rod carries a mandatory visual-limitation disclosure.

⛵Sail & running rigging condition — 1 to 10

10 = new/unused, dropping by remaining cloth-life. Anchored to sailmaker condition ratings; rate each item aboard and mark “Not aboard” for anything not carried.

1–10 — anchored to observable condition, not a guess at “% left”
What sets the score (North Sails; Sailing Totem): UV degradation — thread fails before the cloth, so broken/powdery stitching is the first tell; cloth strength & hand — crisp vs. soft, limp or paper-like; shape — draft crept aft, blown-out or fluttering leech; delamination on laminate sails; chafe at spreaders, patches and reinforcements.
  • 10 New, unused
  • 9 Near-new — crisp cloth, stitching tight, designed shape
  • 8 Light use — minor UV sheen, stitching sound, shape holds
  • 7 Sound working sail — some softening, isolated restitch, good upwind shape
  • 6 Serviceable — visible UV, seam/stitch wear starting, slight draft-aft
  • 5 Fair — cloth softening, multiple seams to address, leech flutter / blown draft
  • 4 Worn — broken stitching in runs, strength down, chafe damage, poor shape
  • 3 Backup — 1–2 seasons; heavy UV / strength loss or delamination starting
  • 2 Poor — delivery/backup only; broad stitch failure, delamination, repaired tears
  • 1 Unserviceable — cloth/laminate failed, not safely usable

Sails

ItemCondition (1–10)Notes
Mainsail
Jib
Genoa
Mizzen
Cutter / staysail
Storm jib / trysail

Running rigging

ItemCondition (1–10)Notes
Halyards
Sheets & control lines
Furling gear
Winches

Sources — sail condition bands: Masthead Sailing Gear & Second Wind Sails remaining-life ratings. Rig inspection & standing-rigging replacement (8–10 yr; professional inspection 3–5 yr): Practical Sailor DIY rig survey; Brion Toss, The Complete Rigger’s Apprentice. Ratings are surveyor judgement — never auto-filled.

🌊§19 · Sea trial

Instrumented. Numbers, not impressions.

Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
General good marine practice
No single standard governs this one - accepted trade practice and surveyor judgement apply.
  • No single standard governs this one.
  • Cite accepted trade practice, a manufacturer figure, or a measurement — and say which.
  • If you cannot cite anything, the honest classification is UNVERIFIABLE.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
Manufacturer specification
The maker's own service data for this model and year. The factory number is the reference.
  • The maker's published figure for this model and year is the reference.
  • Where the OEM publishes a joint spec and a chart gives a different number, the joint spec wins.
  • Record where the number came from — manual, bulletin, or plate — so it can be checked.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.

💷§20 · Summary and valuation

Opinion, clearly labelled as opinion.

Note

This section is opinion and must read as opinion — it is the part of a C&V most exposed to liability. ESI comparables rule: BUC Used Boat Price Guide as the baseline, then SOLD boats rather than asking prices, FIVE comparables preferred, and LOCAL to this market wherever they can be obtained. Record date, location, price and sold-or-asking for every one — a list without those is not evidence. Where you have fewer than five, or had to go outside the region, or could only get asking prices, say so and say what you adjusted for.

ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.

✍️§21 · Closing and certification

Finish as you go — this should be nearly written by the time you step off the boat.

Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
Society report element designation unconfirmed
Element the societies expect in a survey report. Confirm wording against the SAMS Recommended Survey Report Content.
  • Element the societies expect to see in a survey report.
  • Confirm the wording against the SAMS Recommended Survey Report Content once membership grants access.
ESI method observation
No consensus standard governs this point. The finding is still made and cited as an ESI-method observation.
  • No consensus standard governs this point.
  • The finding is still made, and cited as a stated ESI-method observation.
  • Say what the criterion is and why it exists — the reader has never seen it before.

📊§22 · Findings, recommendations and rollups

Generated from the register. Nothing here is typed by hand.

Overall: —

A · Safety deficiencies — red

B · Other deficiencies needing attention — orange and yellow

C · Surveyor notes and observations — blue

System matrix — worst flag per section

Compliance matrix — verified against a cited standard

Scope gaps — every point not inspected, with its reason

Why A / B / C as well as the flags Underwriters and lenders already read survey reports in the A / B / C shape. The six-flag taxonomy is what makes ESI repeatable; the A/B/C rollup is what makes the report readable by the people who already receive them. Same register, two views, no retyping.

📨Issue the report

Build the client report, check it, then send it to the desk.

What goes where Print / Save as PDF produces the client's document — cover, findings, recommendations, compliance matrix and certification. Send to desk files the same survey with the yard as a text record so the desk can track it, chase the outstanding items and issue the PDF.
Plain-text record (what the desk receives)